Feature | Details | ||
Power | Input | 12V±5%,8A Max / 24V±5%,4A Max | Do not exceed 32V Including charging current |
Output | 12V±5%,6A Max / 24V±5%,3A Max |
||
I/O | USB I/F | USB TypeB |
|
RS232C | Terminal block |
||
Misc. | LED | Power(Green), ERR(Red),ALARM(Yellow), Ready(Green) |
|
Switch | Vout ON/OFF switch , Shutdown switch |
||
Battery | LiFePO4 13.2V、2500mA x1(GpUPS32LFP) |
||
Battery life | Expected life 10 years |
1 back UP/da(Ambient temperature=25℃) |
|
Charging time | Less than 5 hours |
Charge from the discharge end voltage |
|
Backup operation | No momentary interruption when switching |
||
Backup time | 20 minutes at load 72W (GpUPS32LFP) |
12V (72W) 2.4C discharge (6A) |
|
Heater | Operates during low temperature charging |
||
Overvoltage protection | Circuit cut off at Vin30V (eFuse) |
||
Overcurrent protection | Circuit cut off at 10A or more (eFuse) |
||
Temperature monitoring | Battery cell unit and BMS board |
||
Environment | Operating Temperature | -20 ~ 60℃ |
At high temperatures (55-60°C), charging protection will be activated. Charging may pause and take longer than the default time. |
Non-Operating Temperature | -20 ~ 55℃ | Recharging may take longer than 3 months. | |
Humidity | 15~90%RH (non-condensation) | ||
Usage environment | Indoor (non-corrosive gas) |
||
Electrostatic discharge resistance | IEC61000-4-2 Level3 (contact) / Level2 (air) | ||
FT/B | IEC61000-4-4 Level2 | ||
Electric field strength | VCCI Class-A (up to 1GHz) | ||
Vibration |
5 to 8.4Hz, amplitude 3.5mm, 8.4 to 150Hz, acceleration 9.8m/s2 *Approximately 100 minutes in each of the X, Y, and Z directions Impact |
Conforms to JIS C 60068-2-6 | |
Impact | Acceleration 147m/s2,Duration 11ms *3 times in each of the X, Y, and Z directions (+ and -) |
Conforms to JIS C 60068-2-27 | |
Dimension | Voltage | 130 x 114 x 110 (mm) | Not including protrusions |
Weight | GpUPS32LFP: 1170g GpUPS64LFP: 1649g |
||
OS | Windows 10(32bit/64bit)・ Windows 11(32bit/64bit) |
Application for displaying and setting |